Generator JP180
GENERATING SET MODEL (JP135)
Output RatingsPrimeStandby
380-415 V, 3 ph, 50 Hz, 1500 rpm180.0 KVA200.0 KVA
144.0 KW160.0 KW
GENERATING SET MODEL (JP150)
Engine MakePerkins
Engine Model1106A-70TAG3
Governing TypeMechanical
Number of Cylinders6
Cylinder ArrangementVertical in line
Bore and Stroke mm105 x 135
Displacement / Cubic Capacity litres7.01
Induction SystemTurbocharged, air to air charge cooled
Cycle 4 stroke
System CombustionDirect Injection
Compression Ratio16:5:1
RotationAnti-clockwise, viewed on flywheel
Cooling SystemWater – cooled
Frequency and Engine Speed50Hz & 1500rpm
PrimeStandby
Gross Engine Power KW (hp)168.8 (226.36)185.7 (249.02)
Fuel Consumption @ 50% load L/hr
@ 75% load L/hr
@ 100% load L/hr
18.8
30.7
39.6


43.7
Total Lubrication System Capacity litres18.018.0
Total Coolant Capacity litres20.520.5
Exhaust Temperature: °C487487
Radiator Cooling Air Flow (Min): m³/sec3.063.06
Combustion Air Flow: m³/min12.7413.45
Exhaust Gas Flow: m³/min30.3732.28
DIMENSIONS AND WEIGHT
Length cmWidth cmHeight cmWeight* Kg (wet)Fuel Tank Litres
257901481702261
DIMENSIONS AND WEIGHT (CLOSED TYPE)
Length cmWidth cmHeight cmWeight* Kg (wet)Fuel Tank Litres
3901111872310320

STANDARD SPECIFICATIONS

1 – ENGINE

Perkins four stroke heavy duty high-performance industrial type Diesel engine.

2 – ENGINE FILTRATION SYSTEM

  • Air filter
  • Fuel filter
  • Full flow lube oil filter
    All filters have replaceable elements

3 – COOLING RADIATOR

Radiator and cooling fan, complete with safety guards, designed to cool the engine at high ambient temperatures.

4 – EXHAUST SYSTEM

Heavy Duty Industrial Exhaust Silencer:
Silencer noise reduction level: 12(dB)
Maximum Allowable Back Pressure: 6.0 (kPa)

5 – CIRCUIT BREAKER TYPE

ABB 3 pole ACB / MCCB (4 pole is optional)

6. FUEL SYSTEM
On Generating Sets up to 650 KVA, the baseframe design is incorporated with an integral fuel tank with a capacity of approx. 8 hours running at Full Load. The tank is supplied complete with full cap breather, fuel feed and return lines to the Engine and drain plug.

7. ALTERNATOR
7.1 INSULATION SYSTEM
– The insulation system is Class H.
– All windings are impregnated in either a triple dip thermosetting liquid, oil and acid resisting polyester varnish or vacuum pressure impregnated with a special polyester resin.
– Heavy coat of antitracking varnish additional protection against moisture or condensation.

7.2 AUTOMATIC VOLTAGE REGULATOR (AVR)
The fully sealed Automatic Voltage Regulator maintains the Voltage Regulation at ±1%. Nominal adjustment by means of a trim pot incorporated on the AVR.

7.3 MOTOR STARTING
An overload capacity equivalent to 300% of the Full Load impedance at zero Power Factor can be sustained for 10 seconds, when PMG option is fitted.

8. MOUNTING ARRANGEMENT
8.1 BASE FRAME
The complete Generating Set is mounted as a whole on a heavy duty fabricated steel Baseframe.

8.2 COUPLING
The Engine and Alternator are directly coupled by means of an SAE  flange. The Engine flywheel is flexibly coupled to the. Alternator rotor.

8.3 ANTI-VIBRATION MOUNTING PADS
Anti-Vibration pads are affixed between the Engine/ Alternator feet and the Baseframe thus ensuring complete vibration isolation of the rotating assembly.

8.4 SAFETY GUARDS
The Fan & Fan Drive along with the Battery Charging Alternator are Safety Guard protected for personnel protection.

9. FACTORY TESTS
* The Generating set is load tested before dispatch
* All protective devices control functions and site load conditions are simulated, The generator and its systems are checked before dispatch.

10. EQUIPMENT FINISHING
All mild steel components are fully degreased and painted with powder coated paint to ensure maximum scuff resistance and durability.

11. DOCUMENTATIONS
Operation & Maintenance manual, Circuit wiring diagrams, and Commissioning / Fault Finding Instruction leaflets are accompanied with the Generator.

12. QUALITY STANDARDS
The equipment meets the following standards: BS4999, BS5000, BS5514, IEC 60034, VDEO530, NEMA MG 1 22 and ISO 8528

13. WARRANTY

All of the Generating Sets are covered under a warranty policy for a period of 12 months. Warranty of the equipment is in line with manufacturers warranty terms & conditions.
(check warranty statement for more details, as it may vary for different countries)

In line with continuous product development, we reserve the right to change specifications without notice.

ALTERNATOR DATA
MakeLeroy Somer
ModelTAL 046A / TAL 044L
No. of bearings1
Insulation classH
Total Harmonic Contentat no load <2.5% / <2%
at linear load <5% / <5%
Ingress ProtectionIP23
Excitation SystemSHUNT
Winding Pitch2/3
AYR ModelR150 / R120
Overspeed2250 min¯¹
Voltage Regulation± 0.8% / ± 1%
Short Circuit Capacity
AREP or PMG Excitation System Available as Optional.
CONTROL PANEL
MakeDeep Sea
ModelDSE6120
The DSE6120 MKIII is an Auto Mains (Utility) Failure Control Module suitable for a wide variety of single
diesel or gas genset applications. It includes a backlit LCD display which clearly shows the status of the
engine all the times. This module can either be programmed using the front panel or by using the DSE configuration suite PC software.

Metering and Alarm indications:
Generator frequency
Underspeed, Overspeed
Generator volts (L-L, L-N)
Generator current
Engine oil pressure
Engine coolant temperature
Fuel level (Warning or shutdown) – Optional
Hours run counter
Battery volts
Fail to start/stop
Emergency stop
Failed to reach loading voltage/frequency
Charge fail
Loss of magnetic pick-up signal – Optional
Low DC voltage
CAN diagnostics and CAN fail/error

STANDARD REFERENCE CONDITIONS
Output ratings are presented at 25°C air inlet temperature, barometric pressure 100 kPa, relative humidity 30%. This generating set is designed to operate at high ambient temperatures (up to 55°C), humidity (up to 99%) and higher attitudes. De-ration may apply, please consult your dealer for specific site ratings.