SUN-5/6/8/10/12K-SG04LP3
  • 100% unbalanced output, each phase; Max. output up to 50% rated power
  • AC couple to retrofifit existing solar system
  • Max. 10 pcs parallel for on-grid and off-grid operation; Support multiple batteries parallel
  • Max. charging/discharging current of 240A
  • Support storing energy from diesel generator
  • 48V low voltage battery, transformer isolation design
  • 6 time periods for battery charging/discharging

Technical Specifications

ModelSUN-5K-SG04LP3-EUSUN-6K-SG04LP3-EUSUN-8K-SG04LP3-EUSUN-10K-SG04LP3-EUSUN-12K-SG04LP3-EU
Battery Input Data
Battery TypeLead-acid or Lithium-ion
Battery Voltage Range (V)40~60
Max. Charging Current (A)120150190210240
Max. Discharging Current (A)120150190210240
Charging Curve3 Stages / Equalization
External Temperature SensorYes
Charging Strategy for Li-Ion BatterySelf-adaption to BMS
PV String Input Data
Max. DC Input Power (W)65007800104001300015600
Rated PV Input Voltage (V)550(160~800)
Start-up Voltage (V)160
MPPT Voltage Range (V)200-650
Full Load DC Voltage Range (V)350-650
PV Input Current (A)13+1326+13
Max. PV ISC (A)17+1734+17
No.of MPP Trackers2
No.of Strings per MPP Tracker1+12+1
AC Output Data
Rated AC Output Active Power (W)5000600080001000012000
Max AC Output Active Power (W)5500660088001100013200
AC Output Rated Current (A)7.6/7.29.1/8.712.1/11.615.2/14.518.2/17.4
Max AC Output  Current (A)8.4/810/9.613.4/12.816.7/15.920/19.1
Max. AC Current (A)11.4/10.913.6/1318.2/17.422.7/21.727.3/26.1
Max Output short circuit current(A) 75
Max. Continuous AC Passthrough (A)45

Peak Power (offff grid)

2 time of rated power, 10 S

Power Factor

0.8 leading to 0.8 lagging
Output Frequency and Voltage50/60Hz;3L/N/PE 220/380Vac,230/400Vac
Grid TypeThree Phase

Total Harmonic Distortion (THD)

<3% (of nominal power)

DC Current Injection

<0.5% In
Efficiency
Max. Efficiency97.60%
Euro Efficiency97.00%
MPPT Efficiency99.90%
Protection
IntegratedAnti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, Output Shorted Protection, Surge Protection
Surge protectionDC Type III / AC Type III
Over Voltage CategoryDC Type II/AC Type III
Certifications and Standards
Grid RegulationVDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150
Safety EMC / StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
General Data
Operating Temperature Range (℃)-40~60℃, >45℃ Derating
CoolingSmart Cooling
Noise (dB)≤45 dB
Communication with BMSRS485; CAN
Weight (kg)33.6
Cabinet Size (WxHxD mm)422×702×281 (Excluding Connectors and Brackets)
Protection DegreeIP65
Installation StyleWall-mounted
Warranty5 Years (10 Years Optional)